7.1 Table of Specifications for Transformation or Arrival Cell 10.5 kVNºDESCRIPTIONUNITVALUE REQUIREDVALUE OFFERED1GENERAL CHARACTERISTICS OF THE SUBSTATION        Substations OropesaHuaroUrpipataOrop

Featured Products

7.1 Table of Specifications for Transformation or Arrival Cell 10.5 kV
DESCRIPTIONUNITVALUE REQUIREDVALUE OFFERED
1GENERAL CHARACTERISTICS OF THE SUBSTATION       
 Substations OropesaHuaroUrpipataOropesaHuaroUrpipata
1.1Nominal operating voltagekV10.510.510 10.510
1.2Altitude of Installationmasl340034001000 34001000
1.3Nominal frequency 60 HZ60 HZ
2GENERAL DATA OF THE EQUIPMENT       
2.1Name of manufacturer    SENDALLSENDALLSENDALL
2.2Model (factory designation)    KYN28KYN28KYN28
2.3Country of origin    CHINACHINACHINA
2.4Construction and test standard IEC 62271-200IEC 62271-200
2.5Category of continuity of service (per IEC 62271-200) LSC2BLSC2B
2.6Partition Classification (per IEC 62271-200) PM 
2.7Internal Arcing Classification (per IEC 62271-200) IAC-AFLRIAC-AFLR
2.8Installation InteriorInterior
2.9Access Frontal; appropriate for mounting on wallFrontal; 
2.1Modular construction Yes; extendible on either sideYes; extendible on either side
3NOMINAL DATA AND CHARACTERISTICS OropesaHuaroUrpipataOropesaHuaroUrpipata
3.1Maximum service voltage of equipmentkV10.510.51010.510.510
3.2Network frequencykV121212121212
3.3Rated current of main barsHz6060
3.4Short-time current (I''k)A63063010006306301250
3.5Short-circuit currentkA252525252525
3.6Duration of short-circuitsec33
3.7Initial crest currentkAp2,5 x I''k2,5 x I''k
3.8Extinguishing medium of the switch VacuumVacuum
3.9Degree of mechanical protection (External) IP  4XIP  4X
3.1Degree of mechanical protection (Internal) IP 2XIP 2X
3.11Auxiliary voltages       
 Control circuitVcc110110
 Spring Load Motor CircuitVcc110110
 Heating circuitVca220220
 Lighting CircuitVca220220
3.12Test Voltages OropesaHuaroUrpipataOropesaHuaroUrpipata
 BIL impulse (1.2 / 50 ms wave)kVp12512595125125125
 Power-frequency (1 min.)kVef505028505050
 Auxiliary circuits (1 min.)kVef22
3.13Main Bars       
 Material CuCu
 Sectionmm2   640640640
3.14Bypass Bars       
 Material Cucucucu
 Sectionmm2   250250250
3.15System Grounding       
 Material CuCu
3.16Painting RAL 7035RAL 7035
3.17Overall Dimensions       
 Width (maximum)mm   100010001000
 Depth (maximum)mm   186018601860
 Maximum heightmm   240024002400
3.18Indication of presence of voltage YesYes
3.19Earthing switch YesYes
4POWER SWITCH       
4.1Manufacturer  SENDALLSENDALLSENDALL
4.2Model    ZN63AZN63AZN63A
4.3Country of origin    CHINACHINACHINA
4.4Standard which corresponds to power switch IEC 62271-100IEC 62271-100
4.5Extinction medium VacuumVacuum
4.6Type of use InteriorInterior
4.7Execution type RemovableRemovable
4.8Type of operation TripolarTripolar
4.9Method of accumulation of operating energy SpringsSprings
4.1Method of loading the springs Motor y manualMotor y manual
4.11Method of opening and closing Manual - electricManual - electric
4.12Maximum number of operation cycles O - 0,3 sec - CO - 15 sec - COO - 0,3 sec - CO - 180 sec - CO
   OropesaHuaroUrpipataOropesaHuaroUrpipata
4.13Nominal voltagekV10.510.51010.510.510
4.14Nominal currentA63063010006306301250
4.15Nominal frequencyHz6060
4.16Permissible short-time current (Icc) (3 sec)kA252525252525
4.17Dynamic current supported in short circuitkAp2,5 x Icc2,5 x Icc
4.18Opening timems33.5..6033.5..60
4.19Arc timems10…1510…15
4.2Total time of cutms43.5..7543.5..75
4.21Close timems60…8060…80
   OropesaHuaroUrpipataOropesaHuaroUrpipata
4.22Power-frequency voltage (60 Hz - 1 min.)kV505028505028
4.23Impulse withstand voltagekV1251259512512595
4.24Starting motor power consumptionWIndicate300W
4.25Rated motor power consumptionWIndicate100W
4.26Power consumption of the opening coilWIndicate100W
4.27Power consumption of the low-voltage coilWIndicate100W
4.28Power consumption of the closing coilWIndicate100W
4.29Motor supply voltageVcc110110
4.3Counter of switching operations YesYes
4.31Auxiliary contacts YesYes
5CURRENT TRANSFORMERS       
5.1Manufacturer    JIANGSUJIANGSUJIANGSU
5.2Model    LZZBJ9LZZBJ9LZZBJ9
5.3Country of origin    CHINACHINACHINA
5.4Construction and test standard IEC 60044-1IEC 60044-1
5.5Insulation type ResinResin
5.6Installation InteriorInterior
5.7Rated VoltagekV10.510.510.510.510
5.8Maximum service voltagekV     
5.9Network frequencyHz6060
5.1Short-time current (3 sec)kA 25252525
5.11Dynamic currentkAp2,5 x Icc2,5 x Icc
5.12Number of Cores 2     
5.13Test Voltages OropesaHuaroUrpipataOropesaHuaroUrpipata
 BIL impulse (1,2/50 mseg.)kVp1251259512512595
 Power-frequency (1 min.)kVef505028505028
5.14Measurement nucleus       
 Current in primaryA600-300600-300600-300600-300
 Current in secondaryA11
 Prestación (considerar una holgura del 30%.)VA5VA5VA
 Precision class 0.20.2
5.15Protection nucelus       
 Current in primaryA600-300600-300600-300600-300
 Current in secondaryA11
 Accuracy classVA5P205P20
 Benefit (consider a 30% slack.) 5VA5VA
6VOLTAGE TRANSFORMERS       
6.1Manufacturer    JIANGSUJIANGSUJIANGSU
6.2Model    JDZJDZJDZ
6.3Country of origin    CHINACHINACHINA
6.4Construction and test standard IEC 60044-2IEC 60044-2
6.5Insulation type ResinResin
6.6Installation InteriorInterior
6.7Rated VoltagekV10.510.51010.510
6.8Maximum service voltagekV1212
6.9Network frequency 6060
6.1Cantidad de secundarios Hz22
6.11Test Voltages OropesaHuaroUrpipataOropesaHuaroUrpipata
 BIL impulse (1,2/50 mseg.)kVp1251259512595
 Power-frequency (1 min.)kVef505028505028
6.12Relation transformation       
 Voltage on the primarykV10.5/√310.5/√310/√310.5/√3 
 Voltage on the secondarykV0.10/√3:0.10/√30.10/√3:0.10/√3
6.13Secondary of measurement       
 Benefit (consider a 30% slack.)VA5VA5VA
 Accuracy class%0.20.2
6.14Secondary of protection       
 Benefit (consider a 30% slack.)VA5VA5VA
 Accuracy class 3P3P
 Voltage factor 1.21.2
7MULTIFUNCTION METER In accordance with table of specifications guaranteedSEL-734
8MULTIFUNCTION RELAY In accordance with table of specifications guaranteedSEL-751+
9.0Grounding switch OropesaUrpipataOropesaOropesaHuaroUrpipata
 Short-circuit capacity YesYesYesYesYES
 Short-time current (I''k)kA2525252525
 Duration of short-circuitsec333333
 Auxiliary contacts normally openunits44444
 Auxiliary contacts normally closedunits444444
 Mechanical lock YesYesYesYesYES
 Interlocking YesYesYesYesYES